Rockwell Automation 2711 PanelBuilder 1200 Transfer Utility User Manual

Page 41

Advertising
background image

Transferring Via the Data Highway Plus

Chapter 4

and Remote I/O

4-15

If the application file has location data defined, this data appears in the
PanelView Location Data fields in the Pass-Through Upload From
PanelView menu.

2

If there is no location data in the application file, or you want to change
some of the fields, you can do so:

a

Enter the necessary information in the Rack, Group, Module and
PLC Type fields.

b

In the PLC DH+ Address, enter a value between 0–77 (octal).

Important

To be able to upload, you must enter a value in this field.

c

Define the Local and Remote Bridge Addresses only if you have two
Data Highway Plus networks joined by a connecting module or
“bridge”.

Defining the Programming Terminal Configuration

Before you can transfer an application file, you must configure your
computer so it can communicate with the Data Highway Plus. You must
define the address of the computer on the network and the type of
hardware driver. For information on selecting the hardware driver, see the
Downloading section earlier in this chapter.

To define the programming terminal configuration:

1

Select Programming Terminal Configuration from the Pass-Through
Upload from PanelView menu.

The Programming Terminal Configuration menu appears.

22573

Programming Terminal Configuration

Programming Terminal DH+ Addres

0

DH+ Hardware Driver

1770-KF2/1785-KE

Pass-Through Utility Directory

C:\AB\PB1200\PTU\PASSTHRU

Quit

Here you can configure the computer’s communications.

Advertising