Troubleshooting

Appendix A

A-4

Important

Only specific models and revisions of PLC controllers are

capable of the Pass-Through download/upload. Refer to the following table
for compatible models and revisions.

Processor

Series

Revision

PLC-5/11

All

All

PLC-5/15

B

N or later

PLC-5/20

All

All

PLC-5/25

A

J or later

PLC-5/30

A

B or later

PLC-5/40

A
B

E or later
B or later

PLC-5/60

A
B

E or later
B or later

PLC-5/250

All

All

Common Error Messages for Manual Address Source Configuration

The following table shows a list of common error messages for Manual
Address Source Configurations.

Message

Cause

What to do

Baud Rate falls outside of this PLC baud rate
range

The selected PLC controller type does not
support the selected Pass-Through baud rate.

Ensure that the Manual Address Source Baud
Rate and the Manual Address Source PLC Type
are compatible. To check compatibility, refer to
the previous table.

Rack Assignment falls outside of this PLC
address range

The selected PLC controller type does not
support the selected Pass-Through rack number.

Ensure that the Manual Address Source Rack
Number and the Manual Address Source PLC
Type are compatible. To check compatibility,
refer to the previous table.

Invalid Rack Number

The selected PLC controller type does not
support the selected Pass-Through rack number.

Ensure that the Manual Address Source Rack
Number and the Manual Address Source PLC
Type are compatible. To check compatibility,
refer to the previous table.

Rack Number must be octal

The rack number must be entered in octal.

Calculate the rack number in octal, and enter
that number.