Converter Parameters

B-3

PowerFlex 1203-USB Converter User Manual

Publication DRIVES-UM001D-EN-P

03

[Clear DF1 Counts]
No action if set to ‘0’ (Ready). Resets the DF1

statistical

Parameter 04 - [DF1 Packets Sent] and

Parameter 05 - [DF1 Packets Rcvd] to 0 (zero) if set

to ‘1’ (Clear Counts). This parameter is a command. It

will be reset to ‘0’ (Ready) after the command has been

performed.

Default:

0 = Ready

Values:

0 = Ready

1 = Clear Counts

Type:

Read/Write

Reset Required: No

04

[DF1 Packets Sent]
Displays the number of DF1 packets sent by the

converter. The value of this parameter is normally

approximately equal to the value of

Parameter 05 -

[DF1 Packets Rcvd].

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

05

[DF1 Packets Rcvd]
Displays the number of DF1 packets received by the

converter. The value of this parameter is normally

approximately equal to the value of

Parameter 04 -

[DF1 Packets Sent].

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

06

[RTU DSI Addr Cfg]
Sets the node address of the converter for use with the

converter operating mode set with

Parameter 01 -

[Adapter Cfg]. In Auto, Master, or Slave mode, the

converter node address can be any valid value. In RTU

Master or RTU Master Passthru mode, the converter

node address must match the address of any drive on

the network. Each network drive address must be

unique. In any case, the RTU DSI address is a decimal

value.

Default:

1

Minimum:

1

Maximum:

247

Type:

Read/Write

Reset Required: Yes

07

[RTU DSI Addr Act]
Displays the node address of the drive that the

converter is communicating with when the converter is

set to RTU Master or RTU Passthru mode using

Parameter 01 - [Adapter Cfg].

Default:

1

Minimum:

1

Maximum:

247

Type:

Read Only

08

[Adapter Type]
Displays the present operating mode for the converter.

Default:

0 = Master

Values:

0 = Master

1 = Slave

2 = RTU Master

3 = RTU Passthru

Type:

Read Only

No. Name and Description

Details