B-4

Converter Parameters

PowerFlex 1203-USB Converter User Manual

Publication DRIVES-UM001D-EN-P

Parameters – SCANport

Drives (DriveExplorer or

DriveExecutive software

only)

No. Name and Description

Details

01

[Adapter Port]
Displays the port on the host drive to which the

converter is connected.

Default:

0

Minimum:

0

Maximum:

7

Type:

Read Only

02

[Reset Module]
No action if set to ‘0’ (Ready). Resets the converter if

set to ‘1’ (Reset Module). Restores the converter to its

factory default settings if set to ‘2’ (Set Defaults). This

parameter is a command. It will be reset to ‘0’ (Ready)

after the command has been performed.

Default:

0 = Ready

Values:

0 = Ready

1 = Reset Module

2 = Set Defaults

Type:

Read/Write

Reset Required: No

03

[Clear DF1 Counts]
No action if set to ‘0’ (Ready). Resets the DF1

statistical

Parameter 04 - [DF1 Packets Sent] and

Parameter 05 - [DF1 Packets Rcvd] to 0 (zero) if set

to ‘1’ (Clear Counts). This parameter is a command. It

will be reset to ‘0’ (Ready) after a ‘Clear Counts’

command has been performed.

Default:

0 = Ready

Values:

0 = Ready

1 = Clear Counts

Type:

Read/Write

Reset Required: No

04

[DF1 Packets Sent]
Displays the number of DF1 packets sent by the

converter. The value of this parameter is normally

approximately equal to the value of

Parameter 05 -

[DF1 Packets Rcvd].

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

05

[DF1 Packets Rcvd]

Displays the number of DF1 packets received by the

converter. The value of this parameter is normally

approximately equal to the value of

Parameter 04 - [DF1

Packets Sent].

Default:

0

Minimum:

0

Maximum:

65535

Type:

Read Only

06

[Interface Mode]
Sets the interface operating mode.
Auto:

The converter will automatically run DPI if

connected to a DPI drive, or SCANport if

connected to a SCANport drive.

SCANport: The converter will perform SCANport

services only.

Set this parameter to ‘0’ (Auto, the default) unless you

are using DriveTools32 software, version 2.xx, and you

are connected to a DPI drive. In this case, use the ‘1’

(SCANport) setting.

Default:

0 = Auto

Values:

0 = Auto

1 = SCANport

Type:

Read/Write

Reset Required: Yes

!

ATTENTION: Risk of injury or equipment damage exists. If the converter is

transmitting I/O that controls the drive (indicated by a steady green diamond

status indicator), the drive may fault when you remove or reset the converter.

Determine how your drive will respond before removing or resetting a connected

converter.