10 direct start with full voltage, Direct start with full voltage -28 – Rockwell Automation Low-Voltage Switchgear and Controlgear User Manual

Page 104

Advertising
background image

100%

Motor
Speed

7 or 15%

Slow
Speed

Start

Run

Stop

Braking

Coast-to-rest

Time (seconds)

Fig. 3.9-11
Soft starters with positioning speed in one direction and controlled braking

100%

Motor
Speed

7% or 15%

Slow
Speed

Start

Run

Time (seconds)

Brake

Slow Speed

Braking

Slow Speed Braking

Coast-to-rest

Fig. 3.9-12
The Accu-Stop™ function enables precise (accurate) positioning in one direction and precise stopping. In
the braking phase, the motor is in a first phase broken until the positioning speed is reached. Complete
braking happens as soon as a stop command is issued.

3.9.9

Linear acceleration and deceleration by speed feedback

Feedback of the motor speed can be used for linear acceleration and stoppage of a drive. The
motor voltage is adjusted – largely independently of the torque requirement of the drive – in
accordance with the speed feedback so that starting and braking follow the selected character-
istic. The resulting motor current is a function of the required voltage.

100%

Percent
Speed

Start

Run

Stop

Time (seconds)

Fig. 3.9-13
Linear acceleration and deceleration of a drive by speed feedback via tachometer.

3.9.10

Direct start with full voltage

Just as with solid state (semiconductor) contactors, a start with full voltage and hence with full
motor torque can be performed with soft starters.

LVSAM-WP001A-EN-P - April 2009

3-28