ƒ Switching-over of supply systems (for example for standby power supplies), for which

complete separation of the two supply systems is required.

ƒ Switching of several single-phase loads (heaters, lamps) with one switchgear unit.
ƒ Switching direct current loads with higher rated voltage that requires the series connection of

four contacts (see also Section

2.4.2

).

2.4.4.2

Applications of switchgear with 2 NO and 2 NC contacts

Devices with two NO and two NC contacts are useful in applications in which one of two circuits
must always be closed. These are, for example
ƒ Switching a heater between two levels (

Fig. 2.4-7

)

ƒ Switching-over between single-phase supplies – for example, emergency power supply

systems (

Fig. 2.4-7

)

ƒ Reversing motors for space saving arrangement of devices (

Fig. 2.4-8

)

ƒ Reversing of 2-step motors with separated windings (

Fig. 2.4-9

)

1

2

Fig. 2.4-7
Four-pole contactors with 2 NO / 2 NC contacts for switching single-phase loads (left) or switching-over
between two supplies (right)

M
3~

I >

L1

L2

L3

V

I / O

Fig. 2.4-8
Slimline reversing starter with a 2 NO / 2 NC contactor for reversing

LVSAM-WP001A-EN-P - April 2009

2-36