Switching-over of supply systems (for example for standby power supplies), for which
complete separation of the two supply systems is required.
Switching of several single-phase loads (heaters, lamps) with one switchgear unit.
Switching direct current loads with higher rated voltage that requires the series connection of
four contacts (see also Section
2.4.4.2
Applications of switchgear with 2 NO and 2 NC contacts
Devices with two NO and two NC contacts are useful in applications in which one of two circuits
must always be closed. These are, for example
Switching a heater between two levels (
Switching-over between single-phase supplies – for example, emergency power supply
systems (
)
Reversing motors for space saving arrangement of devices (
Reversing of 2-step motors with separated windings (
1
2
Fig. 2.4-7
Four-pole contactors with 2 NO / 2 NC contacts for switching single-phase loads (left) or switching-over
between two supplies (right)
M
3~
I >
L1
L2
L3
V
I / O
Fig. 2.4-8
Slimline reversing starter with a 2 NO / 2 NC contactor for reversing