Depending on the time of occurrence of a short-circuit and because of the high inductance of the short-
circuit loop, an overshoot and a high initial current peak are produced.
1

Symmetrical short-circuit current (as an example 50 kA

eff

)

2

Characteristic of the current when switching on at voltage – zero crossover

(most adverse point in time)

u Driving

voltage

This overshoot is taken into account in the regulations by the factor n that should be taken into
account when designing switchgear assemblies with respect to the short-circuit withstand
capacity of the installation and of short-circuit switchgear with respect to its making capacity.
The factor n is depending on the power of the power supply system and therefore on the
prospective short-circuit current (

Tab. 4.1-6

).

r.m.s. value of the

prospective

short-circuit current

[kA]

Power

factor

cos

φ

Factor n

I

≥ 5

0.7

1.5

5 < I

≥ 10

0.5

1.7

10 < I

≥ 20

0.3

2.0

20 < I

≥ 50

0.25

2.1

50 < I 0.2

2.2

Tab. 4.1-6
Standard values for the factor n in accordance with IEC 60439-1 for determining the electrodynamic
short-circuit withstand capacity of switchgear assemblies. The r.m.s. value of the prospective short-circuit
current should be multiplied by the factor n in order to determine the peak value of the prospective short-
circuit current.

4.1.3.2

Effects of and dangers in case of short-circuits

The high currents during short-circuits stress the components in the shorted circuit by high
dynamic forces and strong heat generation in the current-carrying parts.

The forces developed are proportional to the square of the current flowing. Therefore the peak
value of the short-circuit current is highly significant. The heat generation, too, is proportional to
the square of the current.

Usually an electric arc is developing at the location of the short-circuit that can result in serious
injuries to persons through burns, blinding or electric shock as well as it can lead to the damage
or destruction of installation components.