Parameter

Details chapter

Discon

n

ec

to

rs

Fuses

Circuit br

eak

-

ers

Load switch

es

Con

tac

tor

Starters

Rated isolation voltage U

i

2.3.1

P P P P P

Rated operational voltage U

e

(<U

i

)

2.3.2

P P P P P

Rated impulse withstand voltage U

imp

2.3.3

P P P P

Rated operational current I

e

2.3.2

P P P P P

Utilization category

2.3.2

P P P P

Short-circuit withstand capacity / short-circuit
protection

2.3.4

P P P

Rated short-circuit making capacity I

cm

2.3.4.6.1

P

P

Rated short-circuit breaking capacity I

cu

, I

cs

2.3.4.6.2

P P

Cut-off current

2.3.4.2
2.3.4.4

C C

Let-through energy (Joule integral)

2.3.4.1
2.3.4.4

C C

Rated short time current I

cw

2.3.4.3

C C C

Short-circuit coordination
(Type 1, Type 2) with fuses or circuit breakers

2.3.4.5.2

P

Thermal load

2.3.5

P P P P

Ambient temperature

2.3.5.1

C C C C C

Operational overcurrents
(for example heavy-duty starting)

2.3.5.2

C C C C C

Life span

2.3.6

C

C

Frequency of operation

2.3.7

C

C

Rated frequency / harmonics

2.3.8
2.4.3

C C C C C

Safety clearances

2.3.9

P P P

Mounting position

2.3.10

C C

Pollution degree

2.3.3

A A A A A

Overvoltage category

2.3.3

A A A A A

Protective separation

2.3.11

A A A A A

Site altitude

2.3.12

A A A A A

Shock and vibration

2.3.13

A A A A A

Humidity / climatic loading

A A A A A

Chemical ambient influences

A A A A A

Radioactive radiation

A A A A A

UV radiation

A A A A A

External form / IP degree of protection

A A A A A

Tab. 2.3-1
Selection criteria for low-voltage switchgear for main circuits
P … Primary selection factors
C … Complementary selection factors
A … Additional criteria

LVSAM-WP001A-EN-P - April 2009