4 current limiting protective equipment, Current limiting protective equipment -11 – Rockwell Automation Low-Voltage Switchgear and Controlgear User Manual

Page 39

Advertising
background image

breakers with I

n

≤ 2500 A, IEC 60947-2 requires l

CW

≥ 12 · I

n

, at least 5 kA. For I

n

> 2500 A

l

CW

≥ 30 kA is required.

2.3.4.4 Current

limiting protective equipment

If the short-circuit withstand capacity of electrical equipment is lower than the prospective short-
circuit current at the installation site, its loading must be reduced in the case of a short-circuit by
upstream current limiting protective equipment to the permissible magnitude. For this purpose
fuses or current limiting circuit breakers may be chosen.

The I

2

t- and i

D

-values of this protective equipment are – usually in diagrams – stated as a

function of the prospective short-circuit current I

cp

(see example

Fig. 2.3-2

). It should be noted

that these quantities vary with the operating voltage. For fuses, limit-curves can be found in the
diagrams for the cut-off current for the largest and without direct current component (see
example

Fig. 2.3-3

). As the time of occurrence of a short-circuit is coincidental, the cut-off

current for the largest direct current component is critical for engineering (i.e. most unfavourable
time point of occurrence of the short-circuit).

Fig. 2.3-2
i

D

-values and I

2

t-values as a function of the prospective short-circuit current I

cp

When the cut-off current is limited to

≤ 17 kA, in accordance with IEC 60439-1 no verification of

the short-circuit withstand capacity for the downstream circuits is required. This relates in
particular to the mechanical strength of the conductors. For the protection of electrical equip-
ment (for example of motor starters) smaller cut-off currents may also be required.

LVSAM-WP001A-EN-P - April 2009

2-11

Advertising