Rockwell Automation Low-Voltage Switchgear and Controlgear User Manual

Page 82

Advertising
background image

Switching-over itself is usually automatic (rarely manual) and performed by a timing relay set to
the required operating period of the star contactor. Between switching off of the star contactor
and the making of the delta contactor there must be a sufficient time interval to be certain that
the breaking arc in the star contactor is quenched before the delta contactor is switched on. If
switching-over is too rapid, the breaking arc causes a short-circuit and the short-circuit protec-
tion disconnects the circuit (see

Fig. 3.3-3

).

On the other hand, when the switching interval is too long, the motor speed falls during the de-
energized interval, depending on inertial mass and load, so strongly that the in-rush current in
the delta connection is very high, defeating the purpose of the star-delta start up (

Fig. 3.3-4

).

A sufficiently long switching interval between breaking of the star contactor and making of the
delta contactor is achieved in small contactors with short pull-in and dropout times by electronic
timing relays with a switching-over delay of approx. 50 ms. Larger contactors have an inherent
switching delay of > 25 ms. In this case, timing relays without additional switching delay may be
used. The switching interval then is of the optimum length. To avoid phase short-circuits, the
star and delta contactors are additionally mechanically interlocked.

If the delta contactor is switched via an auxiliary contactor (e.g. at low control voltages), no
switching-over delay is required on the time relay. A switching interval of adequate length
results from the sum of the making delay times of the auxiliary and delta contactor.

0.00

1.00

2.00

3.00

4.00

5.00

6.00

I/I

e

0

20

40

60

80

100

n/n

s

[%]

0.00

0.50

1.00

1.50

2.00

2.50

T /T

e

I

Δ

I

Y

T

Δ

T

Y

Fig. 3.3-3
A switching interval that is too short results in a short-circuit via the switching arc – the short-circuit
protection is activated and breaks the circuit

0.00

1.00

2.00

3.00

4.00

5.00

6.00

I/I

e

0

20

40

60

80

100

n/n

s

[%]

0.00

0.50

1.00

1.50

2.00

2.50

T /T

e

I

Δ

I

Y

T

Δ

T

Y

Fig. 3.3-4
With switching intervals that are too long, the speed falls again behind

Æ direct starting in delta connec-

tion

LVSAM-WP001A-EN-P - April 2009

3-6

Advertising