Tripping with three-pole load

Tripping with two-pole load, the middle bimetal strip being unheated

1 = Bimetal strip
2 = Phase failure slide
3 = Overload slide
4 = Differential lever
5 = Contact lever
S

1

= Tripping movement at overload

S

2

= Tripping movement with phase failure

S

3

= Opening the trip contact

Fig. 4.2-11
Principle of operation of the differential release for thermal motor protection relays

For this purpose, motor protection relays have a double slide arrangement in the form of a
phase failure slide and an overload slide. In the case of phase failure, the de-energized, cooling-
down bimetal strip moves the phase-failure slide in the opposite direction to the overload slide.
Via a differential lever, this countermovement is converted into an additional tripping displace-
ment (

Fig. 4.2-11

).

In the event of phase failure, this double slide device causes tripping at a lower current than with
a 3-phase load (characteristic curve b in

Fig. 4.2-13

).

Single-phase operation
For protection of single phase AC current- or direct current loads, all poles should be connected
in series to ensure the force required for tripping the switch mechanism and to prevent tripping
by the phase failure protection (

Fig. 4.2-12

).

Fig. 4.2-12
Series connection of the poles of the motor protection relay for single-phase operation