3.3.1

Normal star-delta starting

Circuit connections and switching-over procedure

On initiation of starting, the supply voltage is applied to the star-connected motor windings. The
starting torque and the starting current in this circuit are approx. 30 % of the values for delta
connection. Because of the reduced torque in star connection, the motor does not quite reach
the rated speed. After star-connected start-up, the windings are switched-over to delta connec-
tion.

Fig. 3.3-1
When starting in star connection, the phase voltage is applied to the motor windings and a windings
current of I

WY

= I

W

Δ

/

√3 flows.

Because of vectorial addition of the windings currents in delta connection I

eY

= I

e

Δ

/3.

On switching from star to delta operation, there is a current surge, whose magnitude depends
on various factors. In the figures below, typical cases are illustrated.

Fig. 3.3-2

shows the ideal case for such a switchover. The motor nearly reaches its rated speed

in the first stage, as the load torque during starting is relatively low. The switching-over current
surge is around the same size as the starting current.

0.00

1.00

2.00

3.00

4.00

5.00

6.00

I/I

e

0

20

40

60

80

100

n/n

s

[%]

0.00

0.50

1.00

1.50

2.00

2.50

T /T

e

I

Δ

I

Y

T

Δ

T

Y

Fig. 3.3-2
Typical characteristic of current and torque for star-delta starting
I = motor

current

I

e

=

rated operational current of the motor

I

Υ

=

current in star connection

I

Δ

=

current in delta connection

I

A

=

current characteristic with star-delta starting

T = torque
T

e

=

rated operational torque of the motor

T

Υ

=

torque in star connection

T

Δ

=

torque in delta connection

T

L

= load

torque

n = speed
n

s

= synchronous

speed

LVSAM-WP001A-EN-P - April 2009

3-5