Rockwell Automation Low-Voltage Switchgear and Controlgear User Manual

Page 12

Advertising
background image

Nature of
current

Category Typical

applications

Relevant
IEC product
standard

AC-20A,

AC-20B

AC-21A, AC-21-B

AC-22A, AC-22B

AC-23A, AC-23B
3)

Connecting and disconnecting under no-load conditions
Switching of resistive loads, including moderate
overloads
Switching of mixed resistive and inductive loads,
including moderate overloads
Switching of motor loads or other highly inductive loads


60947-3

a.c. AC-1


AC-2
AC-3

AC-4
AC-5a
AC-5b
AC-6a
AC-6b
AC-7a

AC-7b
AC-8a

AC-8b

Non-inductive or slightly inductive loads, resistance
furnaces
Slip-ring motors: starting, switching off
Squirrel-cage motors: starting, switching off motors
during running
Squirrel-cage motors: starting, plugging1), inching2)
Switching of electric discharge lamp controls
Switching of incandescent lamps
Switching of transformers
Switching of capacitor banks
Slightly inductive loads in household appliances and
similar applications
Motor-loads for household applications
Hermetic refrigerant compressor motor control with
manual resetting of overload releases
Hermetic refrigerant compressor motor control with
automatic resetting of overload releases







60947-4-1

AC-52a


AC-52b
AC-53a

AC-53b
AC-58a


AC-58b

Control of slip ring motor stators: 8 h duty with on-load
currents for start, acceleration, run
Control of slip ring motor stators: intermittent duty
Control of squirrel-cage motors: 8 h duty with on-load
currents for start, acceleration, run
Control of squirrel-cage motors: intermittent duty
Control of hermetic refrigerant compressor motors with
automatic resetting of overload releases: 8 h duty with
on-load currents for start, acceleration, run
Control of hermetic refrigerant compressor motors with
automatic resetting of overload releases: intermittent
duty





60947-4-2

AC-51


AC-55a
AC-55b
AC-56a
AC-56b

Non-inductive or slightly inductive loads, resistance
furnaces
Switching of electric discharge lamp controls
Switching of incandescent lamps
Switching of transformers
Switching of capacitor banks


60947-4-3

AC-12


AC-13
AC-14
AC-15

Control of resistive loads and solid-state loads with
isolation by optocouplers
Control of solid-state loads with transformer isolation
Control of small electromagnetic loads
Control of a.c. electromagnetic loads


60947-5-1

AC-12


AC-140

Control of resistive loads and solid state loads with
optical isolation
Control of small electromagnetic loads with holding
(closed) current

≤ 0,2 A, e.g. contactor relays

60947-5-2

AC-31A,

AC-31B

AC-33A, AC-33B

AC-35A, AC-35B
AC-36A, AC-36B

3)

Non inductive or slightly inductive loads
Motor loads or mixed loads including motors, resistive
loads and up to 30 % incandescent lamp loads
Electric discharge lamp loads
Incandescent lamp loads


60947-6-1

LVSAM-WP001A-EN-P - April 2009

1-2