external conductors (I

e1

) and the phase currents (I

P1

, I

P2

) in comparison to the case described

above is a factor larger. This factor depends on the load of the motor. The relationships are as
represented in

Fig. 4.1-12

.

Fig. 4.1-11
Current distribution in delta-connected motors in normal operation and with loss of one phase

Fig. 4.1-12
Phase loss of a delta-connected motor. Current flow with symmetrical supply and with phase loss as a
function of the load

IEC 60947-4-1 defines the requirements on the performance of motor protective devices in the
event of a phase loss (

Tab. 4.1-5

). For high quality motor protection temperature-compensated

devices with phase failure protection are standard.