4 effect of long control lines, 1 voltage drop, Effect of long control lines -7 – Rockwell Automation Low-Voltage Switchgear and Controlgear User Manual

Page 159: Voltage drop -7

Advertising
background image

5.3.4 Effect of long control lines

5.3.4.1 Voltage

drop

In accordance with IEC 60947-4-1 and IEC 60947-5-1, the normal control voltage range of
power and control contactors lies between 85 … 110 % of the rated control voltage. Within
these limits contactors pull-in perfectly. Frequently contactors are offered with an extended
control voltage range, thus for example with contactors with electronic coil control. The technical
documentation of the devices used is definitive.

At small control voltages and with long control lines, the voltage drop across the lines to the
contactor (both out-going and return conductors should be considered!) can be so big that
pulling-in reliably is no longer guaranteed. In addition to burnt coils, another consequence of this
may be welding of the main contacts. It must therefore be ensured that taking into account
ƒ Supply voltage variations
ƒ Voltage drop at the control transformer at peak load (see Section

5.2.1.1

) and

ƒ Voltage drop across the control lines
the minimum pull-in voltage is always guaranteed.

For the voltage drop across the control lines the following applies approximately:

A

U

l

S

u

C

R

=

κ

2

100

[%]

or for the maximum line length at a given permissible voltage drop

A

S

U

u

l

C

R

κ

2

max

100

l

Line length (supply and return line) [m]

l

max

maximum line length (feeding and return line) [m]

u

R

Percentage voltage drop [%]

U

C

Rated control voltage [V]

S

Pickup power of the contactor [VA]

κ

Conductivity of the conductor material [m·

-1

·mm

-1

] = 57 for copper

A

Conductor cross section [mm

2

]

1

10

100

1000

10000

10

100

1000

S [VA]

l [m]

24V/0.75 mm2

24V/1 mm2

24V/1.5 mm2

24V/2.5 mm2

110V/0.75 mm2

110V/1 mm2

110V/1.5 mm2

110V/2.5 mm2

230V/0.75 mm2

230V/1 mm2

230V/1.5 mm2

230V/2.5 mm2

Fig. 5.3-5
Line lengths for a voltage drop of 5 % and copper conductors
l

Line length (feeding and return line)

S

Apparent power of load

LVSAM-WP001A-EN-P - April 2009

5-7