Modbus tcp setup submenu, Devices – Banner SureCross DX80 Wireless Networks User Manual

Page 33

Advertising
background image

Modbus TCP Setup Submenu

Use the Modbus TCP Setup pages to specify the network address and optional device parameters of a remote Modbus/TCP device.
Example remote Modbus/TCP devices may include another Gateway device or any remote device using Modbus/TCP to communicate.

Devices

Use the Devices page to set up the network address and optional device parameters for a remote Modbus/TCP device that is linked to for
remote input and/or output.

Map the remote Modbus/TCP device’s input and/or output using the Client Read and Client Write Maps.

Connection Status. Connection status displays a non-zero error code when a socket error occurs. Possible errors include:

• 104 - Connection reset by peer
• 111 - Connection refused
• 113 - Connection aborted
• 114 - Network is unreachable
• 116 - Connection timed out
• 118 - Host is unreachable
• 119 - Connection in progress (connect unsuccessful and still trying)
• 205 - Could not get host IP by name

Default
Poll Peri-
od

The polling period defines how often, in sec-
onds, this device (GatewayPro or Ethernet
Bridge) contacts the device listed and solicits
data.

Domain
Name

The system may also look up an IP address
when given a domain name. If the IP address
is set to zero, the system attempts to find the
host by name.

IP Ad-
dress

Specify the IP address of the remote Modbus/
TCP device.

Local
Name

The local name is an optional field and is used
to refer to this device in other Web Configura-
tor pages.

Port

If port is left set to zero, port 502 is used. To
use a non-standard port number, enter the
number.

Swap
Double
Regis-
ters

The term swapped applies only to double or float
formats. Modbus registers are, by definition, 16
bits of data per register. Access to 32-bit data,
either 32-bit integer (double) or IEEE 754 float-
ing point (float), is supported using two consecu-
tive registers. Modbus protocol is inherently “big
endian,” therefore Modbus defaults to having the
high order register first for double and float for-
mats. If the low order register comes first on the
accessed device, check the Swapped box.

If you have Swapped incorrectly, check the data.
When floating point data is reversed, a 1.0 be-
comes 2.2779508e-41, which rounds to zero. A
floating point 1.1 becomes negative 107609184.
If 32-bit integer data is reversed, 1 becomes
65536.

SureCross Web Configurator

rev. -

www.bannerengineering.com - tel: 763-544-3164

33