To establish calculations, select the operation from the drop list. All operations except logical NOT operations require two operands.
Enter the register numbers as applicable. Some operations are valid for ranges of registers. Select and or thru to select two registers or
multiple registers in a range. Average, sum, and logic operations are valid for ranges of multiple registers.

Constants

Use the Constants tab to define values written once to the assigned registers when the device starts up.

Enter the value and the local register number to which the constant should be written. Each constant writes to the selected register only
once at startup.

Entering zero as the value negates the rule even though it remains in the list until deleted. Unused rules at the end of the list always show
zero as the value. To prevent these from displaying, reduce the number of rules enabled.

Delete
and In-
sert

Clicking the Delete button removes the rule or
map number shown in the Rule # or Map # box.
Clicking the Insert button inserts a new map
ahead of the map number shown. It is not neces-
sary to use the Insert button to add maps to the
bottom of the list or to define any rule with None
as the register type. To add a map/rule to the bot-
tom of the list, increase the number of rules or
maps enabled.

Prev
and
Next

If there are more than 16 devices or rules/maps,
use the Prev and Next buttons to display the next
screen of information.

Up-
date

Clicking the Update button sends information to the
Ethernet Bridge or GatewayPro or retrieves infor-
mation depending on which checkboxes are selec-
ted: Change or Get/Send All. Updating information
does not save configuration information perma-
nently to the XML file.

Setup Submenu

Tabs under the Setup submenu control general system parameters.

Config File

The Config File tab manages the configuration files.

All configuration changes are lost the next time power cycles if you did not click the Save or Save As buttons to write those change to the
XML file in non-volatile memory (Flash file).

When the flash memory updates, there is a delay of several seconds.