Floating point registers, Connection status, Rtu and tcp error codes (a/b format) – Banner SureCross DX80 Wireless Networks User Manual

Page 79

Advertising
background image

• -17: NAMAILC_NOATTACHFILENAME
• -18: NAMAILC_NOATTACHDATA
• -19: NAMAILC_INVALIDATTACHSIZE
• -20: NAMAILC_TOOMANYATTACH
• -21: NAMAILC_INVAILDMAILID
• -22: NAMAILC_INVALIDUSERNAME
• -23: NAMAILC_INVALIDAUTHTYPE
• -24: NAMAILC_INVALIDLENGTH
• -25: NAMAILC_NOMEMORY
• -26: NAMAILC_NOTCONNECTED

Floating Point Registers

The floating point registers associated with each I/O point are assigned based on the following equation: 1000 + I/O# × 2 − 1. For exam-
ple:

I/O Point

Floating Point Register

1

1001, 1002

2

1003, 1004

3

1005, 1006

4

1007, 1008

5

1009, 1010

Connection Status

Connection status displays a non-zero error code when a socket error occurs.

Possible errors include:

• 104. Connection reset by peer
• 111. Connection refused
• 113. Connection aborted
• 114. Network is unreachable
• 116. Connection timed out
• 118. Host is unreachable
• 119. Connection in progress (connect unsuccessful and still trying)
• 205. Could not get host IP by name

RTU and TCP Error Codes (A/B Format)

Error codes (A/B format) indicate the following errors with the first number:

1. n/a for RTU (Transaction ID out of sync)
2. Exception code returned by remote device
3. Function code mismatch (bad packet)
4. Insufficient data (bad packet)
5. No response from remote device, timed out
6. CRC error in received packet

When A is code 2, indicating an exception code was returned, B indicates the exception as follows:

1. Illegal function code
2. Illegal data address (the requested register does not exist in the device)
3. Illegal data value

SureCross Web Configurator