To track a register:

1. Enter the register number to be tracked in the Tracked Register # field.
2. Select destination registers for the Average Register, Min Register, and Max Register, by entering unassigned register numbers in

the supplied fields. Unassigned integer and floating point registers are listed at the bottom of the screen. To automatically assign
the result registers, click the Auto Allocate button. The default starting registers are the first registers not allocated to I/O points.

3. Select how often to reset the statistics from the drop-down list. The reset values can be when logged, daily, or hourly. Selecting

when logged resets the calculations when the values are logged to a file.

4. Enter the time period for the data sampling and the number of slices, or samples, within that time period.
5. Click the Update button to submit the changes.

When tracking any registers, the average, minimum and maximum registers must be assigned. Do not leave these values set to zero
unless no registers are tracked.

The trend data is updated at the period entered and this period is divided into the number of slices, or samples. A sliding window average
of this number of slices is maintained and this filtered value is processed as the trend data. The minimum data value is the average
lowest value for each period sampled. The maximum data value is the average highest value over each period sampled.

All result registers for a given tracked register are reset when any one of the result registers is logged if when logged is selected for reset.
However, all resets are performed after the entire log record has been compiled for the given log cycle to avoid logging partial results.

Delete
and In-
sert

Clicking the Delete button removes the rule or
map number shown in the Rule # or Map # box.
Clicking the Insert button inserts a new map
ahead of the map number shown. It is not neces-
sary to use the Insert button to add maps to the
bottom of the list or to define any rule with None
as the register type. To add a map/rule to the bot-
tom of the list, increase the number of rules or
maps enabled.

Prev
and
Next

If there are more than 16 devices or rules/maps,
use the Prev and Next buttons to display the next
screen of information.

Up-
date

Clicking the Update button sends information to the
Ethernet Bridge or GatewayPro or retrieves infor-
mation depending on which checkboxes are selec-
ted: Change or Get/Send All. Updating information
does not save configuration information perma-
nently to the XML file.