5.5 Creating New Parameter Setup Files (PSFs)

5.5.1 Analysis Mode Assignment

One or two

Measurement Analysis modes

may be programmed.

Meas1

or

Meas2

may be assigned to one or both outputs (Figure 5-8). If

ALL

is selected in either

Analysis mode, all of the scanning information is sent via the serial connection to a

host computer or PLC. The selection of

ALL

does not allow output assignments to be

made to that measurement mode.
The available

Analysis Modes

are listed on page 24 and described on page 28.

5.5.2 Output Programming

The controller offers 2, 3, or 16 outputs, depending on the model. One scan analysis

mode may be assigned to Output #1 and a second, different, analysis mode may be

assigned to Output #2. Programmable output response criteria are described in the

following sections.
All models except the 16-output models have an output labeled

Alarm

. This output

can be programmed to function as the alarm output for the controller’s self-diagnostic

circuitry, whenever a scan analysis mode is not assigned to it. The output may instead

be programmed to serve as a trigger input to begin the scan sequence of another

MINI-ARRAY System.

Models MAC-1, MACP-1, MACN-1, MACV-1, and MACI-1 — Discrete Outputs

The Output Assignments portion of the PSF Configuration screen, shown in

Figure 5-9, allows complete customization of response of the selected Analysis

Mode(s). With the exceptions noted, either Meas1 or Meas2 can be assigned to Output

#1 or Output #2.

Output #2

may be assigned as an Alarm output for the module’s self-diagnostic

circuitry whenever a scan analysis mode is not assigned to it. Output #2 can also be

programmed to serve as a Trigger input to begin the scan sequence of another MINI-

ARRAY System. The Trigger value is the beam location along the array at which the

Trigger output (during a scan) occurs.
Set Point (Low and High) determines where within the array the output(s) will

respond. In the case of total or contiguous beams made or broken, these settings

determine the minimum and maximum number of beams required for an output.

Figure 5-9. Output assignments portion of PSF Configuration screen

Figure 5-8. MINI-ARRAY Software Analysis

Mode Selection