ELR 7000 Series Multi Point Lock

SIgNal

CauSE

TROuBlEShOOTINg

Dark / Unlit

Controller microprocessor is not active

Confirm connections and incoming power

Steady Flashing (GREEN)

Normal operation

Cycle device by closing the timer circuit

Solid Light (GREEN)

Input voltage is dropping out of operating range

Check wire run and power supply output

1 Flashes Followed by Pause (YELLOW)

Retractor sensor problem

Call 800-810-WIRE for assistance

2 Flashes Followed by Pause (YELLOW)

Retractor sensor problem

Call 800-810-WIRE for assistance

3 Flashes Followed by Pause (YELLOW)

Retractor sensor problem

Call 800-810-WIRE for assistance

5. LED Signalling Chart

4.

TIMER MODE Adjustment (Onboard Timer)

How it works: The 24/12 volt input is always energized and the system retracts when the timer input circuit

is closed.
• When the timer circuit is closed utilizing a

momentary switch, the device retracts, remains retracted for a set

duration, and releases. The duration of the retraction is set using an onboard timer setting (0 - 20 second timer

adjustment). The countdown begins when the rail is first retracted.

• When the timer circuit is closed using a

maintain switch, the device retracts.

The device releases when the circuit is re-opened.

Notes:
• Note: 24V/12V supply is constant in

TIMER MODE. The duration of retraction is determined by whichever is

longer: the maintain switch closure or the onboard timer delay.

• If more than 20 seconds delay is necessary (exceeding the maximum setting), an external timer delay relay

is required (not provided).

Note: Refer to Figure. 3 for DIP Switch timer delay settings.

Fig. 3 Timer Delay Settings

(Default = 0 Seconds)

0 Seconds

2 Seconds

3 Seconds

4 Seconds

5 Seconds

10 Seconds

15 Seconds

20 Seconds

1 2 3 4

DELAY

Fig. 3 Settings Location

DIP switch

setting location

Down

Scan to see a

video of this

installation step.