ELR 7000 Series Multi Point Lock

The SARGENT stand alone ELR 7000 series multi point lock is designed to automatically retract the

rods, concealed within the door.

• Certified ANSI/BHMA A156.3 Grade 1
• Fire rated devices available
• UL and CUL listed for use on Fire Doors
• Multi point lock furnished for 1-3/4” doors
• Wire from EAC Panel to door must be shielded

with a drain terminated at EAC Panel controller

Wire Gauge Charts

Total

One-Way

Length of

Wire Run (ft)

Load Current @ 12VDC

1/4A

1/2A

3/4A

1A

1-1/4A

1-1/2A

2A

3A

100

20

18

16

14

14

12

12

10

150

18

16

14

12

12

12

10

200

16

14

12

12

10

10

250

16

14

12

10

10

10

300

16

12

12

10

10

400

14

12

10

500

14

10

10

750

12

10

1,000

10

1,500

10

Total

One-Way

Length of

Wire Run (ft)

Load Current @ 24VDC

1/4A

1/2A

3/4A

1A

1-1/4A

1-1/2A

2A

3A

100

24

20

18

18

16

16

14

12

150

22

18

16

16

14

14

12

10

200

20

18

16

14

14

12

12

10

250

18

16

14

14

12

12

12

10

300

18

16

14

12

12

12

10

400

18

14

12

12

10

10

500

16

14

12

10

10

750

14

12

10

10

1,000

14

10

10

1,500

12

10

7000 Series Multi Point Lock

• Cylinder override available for 7000 CVR with

106 Series Auxiliary Control

12VDC System
• 12VDC ELR Draw = 850mA

24VDC System
• 24VDC ELR Draw = 700mA

General Description

2

Hardware Specifications

3

Electronic Specifications

4

1. Functions

The 7000 ELR can be configured to work in either of two modes:

POWER MODE (see Section II: POWER MODE)

The device is not energized when locked. When electrified, the device and remain in the retracted posi-

tion until power is removed. Power is typically applied through a relay triggered by an access control

device.

TIMER MODE (see Section III: TIMER MODE)

The device is always energized and retraction is triggered by a momentary or maintain switch.

In TIMER MODE:

When the timer circuit is closed using a momentary switch, the device retracts, remains retracted for a set

duration, and releases. The duration of the retraction is set through an onboard timer setting.

When the timer circuit is closed using a maintain switch, the device retracts. The device releases when

the contact is opened.

2. Important

Caution: Disconnect all input power before servicing.

Installer must be a trained and experienced service person.

Wiring must comply with applicable local electrical codes, ordinances and regulations.

3. Installation Notes

Earth Ground: Required for electrostatic discharge (ESD) protection, unless already grounded through

the metal door and frame.