Installing the furnace – Steffes DLF40B User Manual

Page 15

Advertising
background image

For air delivery, the furnace is equipped with a 4­speed supply air blower which is factory wired to operate in 
medium low speed for heating and in medium high speed for cooling and a fan only thermostat setting.  The 
blower speed may be adjusted for lower or higher output requirements.  To do so, change the wiring on the 
blower speed selection terminals located on the supply air blower.  (See the Line Voltage Wiring Diagrams in this 
manual for more information on the wiring and Table 3 for information on duct pressure with regard to blower 
speed.) 

TABLE  3 

Attaching  the  Ducting 

Step  1 

Remove the supply air blower plenum assembly (60) and filter rack (18) from their boxes. 

Step  2 

To access the blower (56), remove the screws from the supply air blower plenum front access cover 
(60) and detach it from the plenum. 

Step  3 

The supply air blower (56) is shipped banded to the plenum assembly (60).  Cut the band to remove 
the blower from the plenum and slide it into the plenum track through the front access. 

Step  4 

Attach the  front access cover to  the plenum. 

Step  5 

Attach the supply air blower plenum assembly (60) to the furnace by drilling two 1/8” holes per edge. 
Attach to the furnace supply air side using the blunt tip screws supplied in the hardware package. 

Step  6 

Secure the filter rack assembly (18) on the return air side, again by drilling 1/8” holes per edge and 
using the blunt tip screws supplied in the hardware package.  A filter should already be included and 
installed in the duct slot of the filter rack assembly. 

Step  7 

Connect both the return air and supply air house ducts to the furnace. 

If  the  furnace  is  installed  in  a  small  enclosed  area,  a  minimum  of  a  24"  x  24"  opening  into 
the  area  where  the  furnace  is  located  must  be  installed  if  not  already  present.    In  addition,  a 
6"  x  6"  non­closing  type  register  must  be  cut  into  the  return  air  duct.  (Refer  to  the  Clear­ 
ance  Requirements  section  of  this  manual  for  more  information.) 

STATIC  PRESSURE  (INCHES  WATER) 

SUPPLY  AIR 

BLOWER  SPEED 

0.10 

0.25 

0.50 

HIGH 

Not  Recommended 

1850 CFM 

1560 CFM 

MEDIUM  HIGH 

1800 CFM 

1780 CFM 

1470 CFM 

MEDIUM  LOW 

1610 CFM 

1580 CFM 

1420 CFM 

LOW 

1230 CFM 

1205 CFM 

Not  recommended 

Installing The Furnace

(cont'd)

14 

(.20 Static Maximum) 

NOTE