Troubleshooting Information

28

BRICK CORE TEMPERATURE TESTING 

An approximate brick core charge level in the furnace can be measured by taking a millivolt reading on the core 
temperature sensor.  This sensor is located on the right side of the storage brick cavity in the limit bar louvre 
area.  (See drawing reference #68 in the Exploded View Parts Diagram.)  The millivolt reading (DC) can be 
compared to the Core Temperature Graph below to correlate the reading to an approximate brick core tempera­ 
ture.  This reading is useful in determining proper core charging of the furnace. 

10 

15 

20 

25 

30 

1400 

1200 

1000 

800 

600 

400 

200 

o 

Co

re 

T

emp

er

at

u

re 

F

Millivolts (DC) 

Maximum  core  charge  temperature  in  normal  operation  is  1350 

F  (nominal). 