Troubleshooting information – Steffes DLF40B User Manual

Page 30

Advertising
background image

29

Troubleshooting Information

(cont'd)

TROUBLESHOOTING GUIDES 

Before starting any of the troubleshooting procedures, check voltage on the load side of all the furnace circuit 
breakers.  Also, check for 24 VAC between each of the 3­amp low voltage fuses and room thermostat terminal 
block “C” position on the charge control circuit board.  These guides are based upon standard configuration of 
the  furnace. 

For  cross  reference  to  number  coded  components  in  each  procedure,  Refer  to  the 
Exploded  View  Parts  Diagram  in  this  manual. 

Air  Delivery 

A.    PROBLEM:  SUPPLY  AIR  BLOWER WILL  NOT  RUN  WITH FAN  ONLY  ROOM 

THERMOSTAT  CALL 

2

NOTE 

Jumper room thermostat connections 

"R" and "G" terminal block positions 

in the charge control circuit board (30). 

Check supply air blower 

relay operation (34). 

(Lower relay in panel.) 

Supply Air Blower 

Will Not Run 

Check wall thermostat 

& field wiring. 

Supply Air Blower Runs 

Check supply air blower relay 

coil voltage for 24 VAC. 

Check supply air blower 

limit switch (54). 

Ok 

Check for 24 VAC between room 

thermostat connection "C" terminal 

block position and the two 3­amp 

low voltage fuses on the charge 

control circuit board (30). 

Replace supply air blower 

relay (34). 

Ok 

No Voltage 

Replace supply air 

blower limit (54). 

Check unit wiring & 

supply air blower motor (58). 

Open 

Ok 

Replace charge control 

circuit board (30). 

Check unit wiring and/or 

replace control 

transformer (28). 

Ok 

No Voltage