Operating the furnace, Cont'd), How to turn the furnace “off” and “on – Steffes DLF40B User Manual

Page 9

Advertising
background image

SUMMER/WINTER 

OUTDOOR AIR 

CHARGE 

kW INPUT (MAX) 

CORE TEMP. 

SWITCH POSITION 

TEMP. (ºF) 

LEVEL 

DLF30B 

DLF40B 

ºF (Nominal) 

Winter 

55* 

9.6 

12.8 

500 

Winter 

35 

19.2 

25.6 

900 

Winter 

15 

28.8 

38.4 

1,350 

Summer 

35 

9.6 

12.8 

500 

Summer 

15 

28.8 

38.4 

1,350 

Operating the Furnace

(cont'd)

8

HOW TO TURN THE FURNACE “OFF” AND “ON” 

Since heat calls are unlikely during the summer months, you may wish to turn the furnace "OFF".  To do so, 
switch all 60 amp core charging breakers located on the front of the furnace’s electrical panel to the "OFF" 
(down) position.  (See Figure 1 for reference to the location of the breakers on the furnace.)  The 15 amp 
breaker should remain "ON" at all times as this breaker operates the blowers and all other controls in the furnace. 
It MUST remain "ON" if using the furnace in conjunction with an air conditioning system.  To turn the furnace 
"ON", switch the breakers to the UP position. 

For users who prefer to maintain a reduced heating capacity during summer months rather than shutting the 
system off completely, the SUMMER/WINTER toggle switch should be set to the SUMMER position.  In 
standard configuration, a SUMMER switch setting enables automatic brick core charging but at a reduced level. 
The outside temperature must drop below 35 

F before core charging will occur.  (Refer to Table 2, Brick Core 

Charging Schedule, in this manual for more information on  charging levels in relation to outdoor temperature and 
the furnace control panel settings.) 

*  If during off­peak hours the wall thermostat calls for heat and the outdoor temperature is above 55 

F, 1/3 of 

the elements will be energized for the duration of the heat call. 

BRICK  CORE  CHARGING  SCHEDULE 

Table  1 

During brick core charging, the heating elements are staged "ON" and "OFF" in 6.4kW increments (maximum). 

The AUTO/HIGH/LOW toggle switch on the furnace control panel will allow the user to override the automatic 
charge control system of the furnace. In normal operation, this switch is set to the AUTO postion. Regardless of 
the position of this switch, the brick core charging system in the furnace is designed to respond to the coldest 
temperature signal it is receiving.  As a result, if the toggle switch is set to LOW and the outdoor sensor is calling 
for a higher brick core temperature setting, the furnace will respond to the sensor signal.  Or, should the charge 
level 1 sensor fail to respond to outdoor temperature, the charge level 2 or 3 sensors will initiate core charging. 
This feature provides control redundancy which reduces the chance of having an uncharged or undercharged 
brick core during cold weather.

Advertising
This manual is related to the following products: