Installing the furnace – Steffes DLF40B User Manual

Page 24

Advertising
background image

9 

See  Figure  16  for  switch  positions  to  complete  steps  6,  7,  and  8.) 

____  6.  In the off­peak mode and with the outdoor air sensor (64) disconnected, jumper 

sensor connection terminals "W" & "R" of the charge control circuit board (30) 
together to perform the following tests: 

____  A.  Set selector switches to SUMMER and AUTO positions.  One 

outdoor sensor light should be on.  Check the unit's charging circuits 
amperages.  On 240V systems, they should read: 

DLF30B  =  40  Amp        DLF40B  =  53  Amp 

____  B.  Set selector switches to WINTER and AUTO positions.  Two 

outdoor sensor lights should be on. Check the unit's charging circuits 
amperages.  On 240V systems, they should read: 

DLF30B  =  80  Amp        DLF40B  =  106  Amp 

____  C.  Set selector switches to WINTER and HIGH position.  Three outdoor 

sensor lights should be on. Check the unit's charging circuits 
amperages.  On 240V systems, they should read: 

DLF30B  =  120  Amp        DLF40B  =  160  Amp 

____  D.  Simulate an on­peak period by changing the status of the blue and blue/white wires.  All 

heating elements (17) should cycle off. 

To  perform  Step  7,  the  peak  override  feature  must  be  enabled.    This  feature  may  not  be  avail­ 
able  in  your  area.    Please  consult  your  power  company  if  you  are  unsure  of  whether  this  option  is 
available  to  you.    If  it  is  available  and  you  desire  to  enable  the  feature,  contact  your  power 
company  for  instructions  on  how  to  do  so.    Skip  Step  7  if  the  peak  override  feature  is  not  avail­ 
able  to  you.
 

____  7.  With unit in the on­peak mode, depress the override "START" switch and observe the "OVERRIDE" 

indicator light.  The light should be illuminated. 

____  8.  Remove the jumper between  the "W" and "R" outdoor sensor connection terminals and reconnect the 

outdoor air temperature sensor (64).  Set the selector switches to the AUTO and WINTER positions. 

____  9.  Replace the electrical panel cover (46), make certain all fuses and/or circuit breakers are labeled in the 

service  panel. 

____ 10.  Present owner with the manual and warranty information.  The owner's registration card must be com­ 

pleted and  returned to Steffes Corporation to ensure warranty coverage. The owner should retain the top 
portion of the card for their records. 

____ 11. Take the time needed to instruct the owner on how to operate the system. 

23

Installing The Furnace

(cont'd)

FURNACE FINAL TEST PROCEDURE 

____  1.  Check all electrical connections for proper termination placement and do a general inspection for tight 

connections, wire routing, etc. 

____  2.  Energize  the  furnace. 

____  3.  If the wall thermostat has an anticipator, set the anticipator 0.5 amps. 

____  4.  Turn up wall thermostat to bring on a call for heat.  Core blower (38) should run on its high speed with a 

cold brick core.  Because the brick core is cold, the supply air blower (58) will not run in this mode. 

____  5.  If the thermostat is equipped with a mode selection switch, set to FAN ONLY, and check for medium high 

speed (cooling) supply blower (58) operation. 

NOTE 

FIGURE  16 

NOTE