Troubleshooting Information

(cont'd)

33 

B.    PROBLEM:    FURNACE  WILL  NOT  CHARGE  (FURNACE  HAS  NO  CORE  CHARGE)  continued... 

Check for 24 VAC 

across L1 and L2 on the 

auxiliary control board. 

Verify polarity of the red and yellow 

thermocouple wires connected to the 

auxiliary control board. Red should be 

connected to "TC­" and yellow should 

be connected to "TC+". 

Check unit wiring. 

24 VAC 

No Voltage 

Jump "TC­" and "TC+" 

terminals on auxiliary 

control board. 

Fix wiring. 

Incorrect 

Ok 

Charge 

Light "ON" 

Check continuity across 

the red and yellow 

thermocouple wires. 

Replace auxiliary 

control relay board. 

Charge 

Light "OFF" 

Replace the 

thermocouple. 

Contact 

Steffes 

Technical 

Support. 

No Continuity 

Continuity 

NOTE 

This portion of the troubleshooting flow chart is to test operation of the auxilairy control board. 
Furnaces built after January of 1998 were produced with this additional control. If a system built 
before 1998 experiences element failure, Steffes recommends that the auxiliary control board be 
added as a supplemental controller for monitoring core temperatures in systems which have ele­ 
ment failure.