Installing the furnace – Steffes DLF40B User Manual

Page 22

Advertising
background image

FIGURE  13 

Mounting  and  Wiring  Connections: 
Step  1
 

Attach the thermostat to a wall.  Insulate the opening through which the thermostat wires runs. 
Failure to do so may affect the accuracy of the thermostat. 

Step  2 

Disconnect power to the furnace and route  low voltage wire between the thermostat and 
the  furnace. 

Step  3 

Route the wire into the furnace’s electrical compartment and to the front of the charge control circuit 
board (30). 

Never  install  any  wiring  in  the  line  voltage  compartment  of  the  furnace  unless  it 
is  rated  for  line  voltage. 

Step  4 

Connect the thermostat to the 4 position terminal strip on the top front left corner of the charge 
control circuit board (30) labeled “R”, “W”, “G”, and “C”.   (See Figure 13 for reference to room 
thermostat  connections  to  the  furnace.) 

Step  5 

If the thermostat has an anticipator, set it to .5 amps. 

Installing The Furnace

(cont'd)

21

NOTE 

NOTES:  1.  Wiring  shown  is  for  use  with  N.O.  (switch  closes  to  charge)  load  control  device.    Y  and  Y2 

would  be  used  with  a  N.C.  system  (switch  opens  to  charge). 

With  Uncontrolled 

Air  Conditioning 

With  Utility  Controlled 

Air  Conditioning