Changing the bank number of sensor amplifiers, 2 i/o communication, Co mm u ni c a ting w ith t he g t 2 s er ie s – KEYENCE DL-DN1 User Manual

Page 49

Advertising
background image

3-2 I/O Communication

3-19

3

Co
mm

u

ni

c

a

ting
w

ith t
he G

T

2

s

er

ie

s

- DeviceNet Compatible Network Unit DL-DN1 User’s Manual (GT2) -

Changing the Bank Number of Sensor Amplifiers

Device assignments:

"Changing a bank" (page 3-13)

This example changes the bank number associated with ID01 and ID02.
It assumes that the operating mode assigned to the device is 3-output mode.
(1) Specify a new bank number in "select bank number" and execute "request to

change bank"(0 -> 1). In this example, the bank is changed for both ID01 and ID02
simultaneously.

(2) The "bank change complete" signal flips from 0 to 1 when the change to the

specified bank number is completed.

(3) The "bank change error" signal flips from 0 to 1 if an error occurs during the bank

change process. Check the value specified in the "select bank number" parameter.

(4) When the "request to change bank" command is set to 0, the "bank change

complete" and "bank change error" parameters flip to 0.

• The DL-DN1 is disabled from bank changing if the sensor amplifier

is in the key locked state.

• Set the simultaneous input setting of the sensor amplifiers to indi-

vidual input.

PLC

Select bank number

1 (Bank 1)

3

Out area [m+4]

Request to change bank of ID 01

Out area [m+3] BIT 0

Request to change bank of ID 02

Out area [m+3] BIT 1

(2)

Completed in changing bank of ID 01

IN area [n+7] BIT 0

Completed in changing bank of ID 02

IN area [n+7] BIT 1

(3)

Bank change error of ID 01

IN area [n+8] BIT 0

Bank change error of ID 02

IN area [n+8] BIT 1

Sensor amplifier

Bank number of ID 01

1 (Bank 1)

Bank number of ID 02

1

3

1
0

1

0

1
0

1

0

1

0

1

0

(1)

(4)

(Bank 1)

(Bank 3)

(Bank 3)

Point