2 e8 controller fault codes, Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual

Page 105

Advertising
background image

MODULEX EXT

1530, 1912, 2295, 2677, 3060 BOILERS

Installation, Operation & Maintenance Manual

6.1.2 E8 Controller Fault Codes

The table below lists the fault codes and fault descriptions associated with the E8 Controller.

Table 6-2: E8 Controller Fault Codes

CODE

DESCRIPTION

EFFECT

CORRECTION

RESET

PCB Element Fault

E 1

Intervention of the

high limit thermostat

(TL).

Boiler shuts off.

Check for any obstructions

in the piping. Ensure

sufficient flow.

MANUAL - Pushbutton

under cap, located to the

left of the E8 controller.

E 2

Insufficient gas

pressure.

Boiler will not run.

Check gas supply to the

unit and ensure minimum

3.5" w.c. at high fire

AUTOMATIC

E 4

No flame detected

during the ignition

phase.

Boiler will not remain

lit after 3 attempts.

Watch ignition through

viewport. Ensure correct

120V wiring to the unit.

Clean or replace flame rod.

MANUAL - Clear fault and

retry ignition.

E 5

Loss of flame signal

during boiler

operation.

Boiler fails after

establishing flame

Ensure sufficient gas

pressure and flow during

high fire operation and

with any other connected

gas equpiment running.

Check and clean flame rod.

AUTOMATIC - Clear fault

and retry ignition.

E 6

Over high water

temperature detected

by the heating sensor

(SR) (>203°F).

Boiler shuts off.

Check for any obstructions

in the piping. Ensure

sufficient flow.

AUTOMATIC - After

temperature falls.

E 10

Internal failure of the

local control PCB

(BMM).

Module shuts off.

Shut off power to the

boiler. Check fuse on

BMM. Replace BMM if

necessary.

AUTOMATIC - After turning

power on to the unit.

E 11

Flame signal detected

before the ignition

cycle.

Boiler will not

attempt ignition.

Allow flame rod to cool.

Possibly replace flame rod.

MANUAL - Clear fault and

retry ignition.

E 12

Local flow sensor

failure SR1 first

module.

Module will not run.

Check with multimeter and

replace if necessary.

AUTOMATIC

E 14

Failure of the heating

return sensor (SRR).

Module will not run.

Check with multimeter and

replace if necessary.

AUTOMATIC

E 15

Difference between

the global return

heating temperature

global sensor and the

heating flow sensor

greater than (>) 86 °F

(rp +10).

Boiler shuts off and

pump turns on at max

speed.

Check for any obstructions

in the piping. Ensure

sufficient flow.

AUTOMATIC - When ΔT <

protection temperature

OMM-0095_0E