MODULEX EXT

1530, 1912, 2295, 2677, 3060 Boilers

Installation, Operation & Maintenance Manual

7.5 Visual Inspection of the Flame

(2 and 4 year maintenance)

The burner must flame evenly over the entire surface when operating correctly. The flame must

burn with a clear, ORANGE, stable flame. Check the flame through the flame observation port

(Figure 7-2). The flame pattern should resemble the flame in the illustration below.

7.5.1 FLAME COLOR:

YELLOW

= CO

2

HIGH NOT SATISFACTORY

BLUE

= CO

2

LOW NOT SATISFACTORY

ORANGE

= OK

SATISFACTORY


Figure 7-2: Boiler Flame Observation Port Location

7.6 Proper Reassembly and Resealing of the Vent-Air Intake System

After removing, inspecting, and possibly cleaning the flue pipes and air intake, replace the

piping correctly. Refer to AERCO’s Modulex Venting Application Guide (GF-136-V) for

information concerning Modulex venting requirements.