MODULEX EXT

1530, 1912, 2295, 2677, 3060 Boilers

Installation, Operation & Maintenance Manual

Figure 3-14: Flue Exhaust Diameter Reduction Adaptor Kit

Table 3-3: Vent Part Numbers

Model

Dia.

Material

Part Number

EXT 1530

EXT 1912 10”

Stainless

Contact vent manufacturer

Polypropylene Contact vent manufacturer

PVC

58115-1

EXT 2295

EXT 2677

EXT 3060

12”

Stainless

Contact vent manufacturer

Polypropylene Contact vent manufacturer

PVC

58115-2

In the case of PVC venting, the flue venting pipe is affixed to the adapter using RTV liquid

silicone and then clamped with a worm-driven Hose Clamp.
When using non-metallic (plastic) venting materials, use schedule 40 or thicker, single-wall,

uninsulated pipes. When using non-metallic (plastic) vent systems for Canadian installations,

per CSA B149.1, use vent systems that are certified to the standard for Type BH Gas Venting

Systems, ULC-S636.
Please note that 10” and 12” PVC can be heavy and expensive. Alternative vent materials, such

as AL29-4C or polypropylene should be considered prior to installation.
The plastic components, primers and glues of the certified vent system must be from a single

system manufacturer and not mixed with other manufacturer’s vent system parts.

GASKET

EUROPEAN-TO-USA

STANDARD FLUE ADAPTER

DIAMETER REDUCTION

ADAPTOR CONNECTOR

WORM-DRIVEN HOSE CLAMP

WASHERS (8 EACH)

SCREWS (8 EACH)

FLUE MANIFOLD

Example Vent Starter Piece

ACCESS POINT FOR

CLEANING (underneath)