Table 6-2: E8 Controller Fault Codes (Continued)

CODE

DESCRIPTION

EFFECT

CORRECTION

RESET

E 16

Boiler body

temperature very low:

Ice forming risk

Boiler will not run.

Pump runs for 5

minutes.

Carefully defrost boiler.

AUTOMATIC - when

sensor is >41°F

E 20

Flame signal detected

after burner is OFF.

Boiler will not run.

Allow flame rod to cool.

Possibly replace flame rod.

MANUAL - Push reset

switch or cycle power.

E 24

Modulating fan speed

failure: failed to reach

the correct speed

within 30 seconds

from starting of

burner ignition cycle.

Boiler will not

ignite.

Check Expert HS fan speed

settings. May require a new

blower.

AUTOMATIC

E 26

Modulating fan speed

failure: failed to stop

within 30 seconds

from end of operation

Boiler will not

ignite.

Check Expert HS fan speed

settings. Check fan wiring. May

require a new blower.

AUTOMATIC

E 28

Common chimney

obstruction.

Boiler will not run.

Check pressure in chimney

during operation. Ensure hoses

to pressure switches are clear.

MANUAL

E29

Water inside exhaust

chamber.

Boiler shuts off.

Check for backed up

condensate in exhaust

manifold. Clean p-trap and

condensate drain line. Check

float sensor in exhaust

manifold for proper operation.

AUTOMATIC

E 30

Alteration of the

operating parameters

caused by EMC

disturbances.

Boiler will not run.

Pump runs for 5

minutes.

Re-program settings. Contact

factory.

MANUAL - Push reset

switch or cycle power.

E 32

Mains supply voltage

< 108 VAC.

Boiler shuts off/will

not run.

Check supply voltage.

AUTOMATIC

E 40

Low water flow.

Boiler shuts off/will

not run.

Check water flow, flow switch

(or LWCO) operation.

AUTOMATIC

E 41

Presence of air in the

pump (only with

SensorLogic)

n/a

n/a

n/a

E 42

Pump blocked (only

with SensorLogic)

n/a

n/a

n/a

E 43

Pump wire failure

(only with

SensorLogic)

n/a

n/a

n/a

Page 106 of 138