CHAPTER 7: MAINTENANCE SCHEDULE

The boiler must receive regular maintenance and cleaning in order to ensure reliable and

efficient operation. Regular maintenance will prolong the life of the boiler. Refer to Table 7-1 for

a suggested schedule of maintenance procedures.
The frequency of servicing will be determined by the service engineer and will depend on the

appliance’s condition.

CAUTION!

To ensure the continued safe and efficient operation of the boiler it

is highly recommended that it be checked at regular intervals and

serviced when necessary, and that only original spare parts be

used. Regular maintenance will prolong the life of the boiler.

WARNING!

If the boiler is not checked and serviced regularly it could cause

damage to the equipment and/or harm to persons.

Table 7-1: Modulex EXT Maintenance Schedule

Maintenance Operation

Check Once

a Year

Check Every

2 Years

Inspect for acceptable circulating and feed water quality

and chemistry.

Inspect gas assembly components.

Inspect safety devices for water and gas.

Inspect and clean the combustion chamber & 8 burners

Inspect and clean flame rod and ignitor.

Inspect and clean the fan/blower.

Check the operation of the fan/blower.

Check gas pressure and adjust if necessary.

Inspect and clean the flue exhaust assembly.

Check all water connections and valves.

Do combustion analysis and recalibrate if necessary.

Check electrical and electronic components

Inspect condensate drain and P-trap, clean if necessary.

Check flow switch in CSD-1 manifold for proper function