2 room air combustion, 3 sealed combustion, Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual

Page 40

Advertising
background image

MODULEX EXT

1530, 1912, 2295, 2677, 3060 Boilers

Installation, Operation & Maintenance Manual

WARNING!

Fire danger due to flammable materials or liquids. Do not store

flammable materials and liquids in the immediate vicinity of the

boiler.

CAUTION!

See Section 3.7.2 for warnings and guidelines concerning materials

and contaniments that should be avoided in the boiler room and

near air inlets when operating the boiler.

3.21.2 Room Air Combustion

The boiler room shall be provided with two permanent openings communicating directly with an

additional room(s). The total input of all gas utilization equipment installed in the combined space

shall be considered in making this determination. Each opening shall have a minimum free area of

1 square inch per 1,000 Btu per hour of total input rating of all gas utilization equipment in the

confined space, but no less than 100 square inches. One opening shall commence within 12

inches (305 mm) of the top, and one opening shall commence within 12 inches (305 mm) of the

bottom of the enclosure. The minimum dimension of air openings shall not be less than 4 inches

(101.6 mm).

3.21.3 Sealed Combustion

The boiler room shall be provided with two permanent openings, one commencing within 12

inches (305 mm) from the top of the enclosure, and one commencing within 12 inches (305 mm)

from the bottom of the enclosure. The openings shall communicate directly, or by ducts, with the

outdoors or spaces (crawl or attic) that freely communicate with the outdoors. The minimum

dimension of air openings shall be no less than 4 inches (101.6 mm).

1. Where directly communicating with the outdoors, each opening shall have a minimum free area

of 1 square inch per 4,000 Btu/hr of total input rating of all equipment in the enclosure.

2. Where communicating with the outdoors through vertical ducts, each opening shall have a

minimum free area of 1 square inch per 4,000 Btu/hr of total input rating of all equipment in the

enclosure.

3. Where communicating with the outdoors through horizontal ducts, each opening shall have a

minimum free area of 1 square inch per 2,000 Btu/hr of total input rating of all equipment in the

enclosure.

4. Where ducts are used, they shall be of the same cross-sectional area as the free area of the

opening to which they connect.

Page 40 of 138

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0095_0E

12/01/14

Phone: 800-526-0288

GF-139