Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual

Page 112

Advertising
background image

MODULEX EXT

1530, 1912, 2295, 2677, 3060 Boilers

Installation, Operation & Maintenance Manual

Table 6-4: BMM Fault Codes (Continued)

CODE DESCRIPTION

EFFECT

CORRECTION

RESET

E 24

Fan speed out of

control: It

doesn't reach

pre-purge speed

within 30

seconds.

Ignition retry

after 60

second delay

and failure

remains until

we have a

successful

burner

operation.

Check fan wiring.

AUTOMATIC/MANUAL

E 26

Fan speed out of

control: It

doesn't stop

within 30

seconds after

turned OFF.

Ignition is

inhibited.

Check fan wiring.

AUTOMATIC

E 27 Air flow failure

during ignition.

Restart pre-

purge timer.

The failure

remains until

we have a

successful

burner

operation.

Check fan and wiring.

Check air proving switch

and wiring.

AUTOMATIC

E 30 Settings

corrupted.

Ignition is

inhibited.

Pump runs for

5 min at max

speed.

Re-program the settings.

Contact factory.

MANUAL - cycle the

power or send reset

message.

E 32 Line voltage too

low (<96 VAC).

Wait for

proper line

voltage (>102

VAC).

Check input voltage. Try

another BMM.

AUTOMATIC

E 40

Low water flow.

Low water flow

switch activated.

Burners

turned OFF.

Check water flow or

check switch.

AUTOMATIC




Page 112 of 138

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0095_0E

12/01/14

Phone: 800-526-0288