Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual

Page 111

Advertising
background image

MODULEX EXT

1530, 1912, 2295, 2677, 3060 BOILERS

Installation, Operation & Maintenance Manual

Table 6-4: BMM Fault Codes (Continued)

CODE DESCRIPTION

EFFECT

CORRECTION

RESET

E 14 Return sensor

fault.

All burners

turned OFF.

Check return sensor or

wiring.

AUTOMATIC

E 15

Maximum Δ-

temperature

protection.

Flow

temperature -

Return

Temperature >

Water Δ-Temp

Protection +

50°F.

All burners

turned OFF

and Pump ON

at maximum

speed.

Check the system

installation.

AUTOMATIC -

when Δ-

temperature <

Water Δ-Temp

Protection.

E 16

Boiler pipe is

frozen. Flow

sensor

temperature is

36°F or less.

Ignition is

inhibited. Pump

runs for 5 min

at max speed.

Carefully defrost boiler.

AUTOMATIC -

when flow sensor is

greater than 41°F.

E 20

Flame signal

detected after

burner is OFF.

Ignition is

inhibited.

Disconnect gas valve wire

from BMM. If failure goes

away, check wiring or

change BMM. If failure

remains, check or change

gas valve.

MANUAL - push

reset switch or

cycle power.

E 22

No air flow at

burner after fan

started for 30

seconds.

Ignition retry

after 60 second

delay and

failure remains

until a

successful

burner

operation.

If fan is stopped, check

supply voltage and fan

wiring. If OK, try another

fan. If still not working,

change the BMM.

If fan is not stopped, check

the exhaust gas outlet for

blockage. If OK, check the

air pressure switch wiring. If

still not working, try another

air pressure switch. If still

not working, change the

BMM.

AUTOMATIC/MAN

UAL

E 23

The air

pressure switch

doesn't switch

off.

Ignition is

inhibited.

Disconnect the air proving

switch. If problem goes

away, install a new switch.

If not, check the wiring. If

wiring is OK, change BMM.

AUTOMATIC




OMM-0095_0E

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

Page 111 of 138

GF-139

Phone: 800-526-0288

12/01/14