1 cleaning the condensate drain line, 4 checking csd-1 manifold flow switch, Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual

Page 115

Advertising
background image

MODULEX EXT

1530, 1912, 2295, 2677, 3060 BOILERS

Installation, Operation & Maintenance Manual

7.3.1 Cleaning the Condensate Drain Line

In order to inspect and clean the condensate line, do the following:

1. Refer to Figure 7-1, disconnect the pipe at location “A“.
2. Check that no deposits have accumulated inside the drain. If there are any deposits flush

them out with clean water.

3. Reassemble the drain in reverse order.

Figure 7-1: Condensate Drain Location

WARNING!

Before operating the boiler, it is absolutely necessary to verify that

the condensate P-trap is filled with water. If the boiler is operated

without the P-trap being properly filled, there is a danger of toxic

combustion gases escaping from the unfilled condensate drain

opening.

7.4 Checking CSD-1 Manifold Flow Switch

Check the function of the flow switch in the CSD-1 manifoild at the boiler hot water outlet. If it is

not functioning, check the wiring to the terminal of the BMM module labeled “FL“ or replace with

a new flow switch.

OMM-0095_0E