1530, 1912, 2295, 2677, 3060 BOILERS

Installation, Operation & Maintenance Manual

3.37 Conversion from Natural Gas to Propane Gas

To convert the unit to use propane gas, instead of natural gas, do the following:

Converting From Natural Gas to Propane Gas

1. Set nominal heat by adjusting the fan speed parameter FH (FAN MAX) from the E8

controller as shown in Table 3-7, MODULEX EXT Pressure and CO

2

Level Calibration

Tables in section 3.3. This parameter requires a password to change.

2. Adjust CO

2

(%) minimum and maximum levels according to the type of gas as shown in the

table below. See section 3.33 - Burner Calibration, above, for more information.

Gas Type

CO

2

Level (%) Minimum CO

2

Level (%) Maximum

Natural Gas

8.5

10

Propane Gas

10

11

3.

After gas conversion to propane and calibration, the gas installer should complete and apply

this label, or equivalent, as close to the rating label as possible:

Figure 3-33: MODULEX EXT Label

OMM-0095_0E