Modulex ext – AERCO Modulex EXT 1530 - 3060 User Manual

Page 98

Advertising
background image

MODULEX EXT

1530, 1912, 2295, 2677, 3060 Boilers

Installation, Operation & Maintenance Manual

Table 5-6: EXPERT Menu

LEVEL

DESCRIPTION

ENTRY

INSTALLATION

DEFAULT

RANGE

BUS-ID HS

Boiler Bus address only for cascade of E8

controllers

----

(01 ÷ 08)

BUS ID 1

The heating circuits are sequentially numbered.....

01

(01 ÷ 15)

BUS ID 2

The heating circuits are sequentially numbered.....

--

(01 ÷ 15)

AF SUPPLY

Outdoor sensor power supply

01

(01 ÷ 15)

BUS TERM

Bus terminating resistor

01

(00 ÷ 01)

EBUS SUPPLY

Switching eBUS supply on/off in realtion to

connected

01

(00 ÷ 01)

TIME MASTER

00 no time master; 01 controller is time master

00

(01 ÷ 01)

MAX T-COLL

Protects the HS from overheating

176°F

(86 ÷ 230)

MIN T-COLL

Decreased condensation build-up in HS with low

heat requirement

50°F

(50 ÷ 176)

MAX T-HS2

Protects the HS from overheating

185°F

(86 ÷ 230)

MIN T-HS2

Decreased condensation build-up in HS with low

heat requirement

104°F

(50 ÷ 176)

V-CURVE

Only for 0-10V input/output

11

(00 ÷ 11)

CURVE 11 - U1

Low voltage set

0 V

(0 V÷10 V)

CURVE 11 - U2

Higth voltage set

10 V

(0 V÷10 V)

CURVE 11 - T1

Low temperature level

68°F

(32 ÷ 248)

CURVE 11 - T2

High temperature level

185°F

(32 ÷ 248)

CURVE 11 - UA

Starting with this voltage level

2 V

(0 V÷10 V)

HYSTERESIS

Dyn. Switching hysteresys stage 1

9

(4Ra÷36Ra)

FOUND MODULS

Display of burners automatically reported via

BUS

0

(0÷30 min)

CAP/MODULE

After restarting the controller searches the bus

systems

----

(0÷1000)

NEW CONFIG

New bus configuration

(00 ÷ 01)

MIN MOD CASC

Min. modulation cascade

0

(00 ÷ 100)

HW-BOILER

Number of stages for HW operation

0

(00 ÷ 08)

CONTR DEVIAT

Header control variance

(00 ÷ 08)

DES OUPUT

Required system output [in %]

(0 ÷ 100)

BLOCK TIME

Currently remaining value

MAX T-MODUL

Maximum temperature of the heat generator

185°F

(122 ÷ 230)

DYN UPWARD

Dynamic heat generator connection

100

(20 ÷ 500)

DYN DOWNWARD

Dynamic heat generator deactivation

80

(20 ÷ 500)

RESET TIME

Resetting time for I-Controller

180

(5 ÷ 500)

Page 98 of 138

AERCO International, Inc. • 100 Oritani Dr. • Blauvelt, NY 10913

OMM-0095_0E

12/01/14

Phone: 800-526-0288

GF-139

Advertising