MODULEX EXT

1530, 1912, 2295, 2677, 3060 Boilers

Installation, Operation & Maintenance Manual

Table 4-6: BCM 3-Position and 2-Position Switch Functions

2-Pos Switch

(Enable/Disable)

3-Pos Switch

(I/O/II)

Position I

(NOTE 1)

Position O

(see NOTE 2)

Position II

(See NOTE 3)

O = OFF (Disable)

DO NOT USE

The BCM is the Gate-way for

Modbus and external control.

The E8 does

not control the

boiler and the BCM will

not

take over the boiler if the

Modbus signal fails.

The E8

is the primary

controller and the BCM

allows monitoring through

Modbus, but

will not take

over boiler if the E8 fails.

I = ON (Enable)

DO NOT USE

The BCM is the Gate-way for

Modbus and external control.

The E8 does

not control the

boiler and the BCM

will take

over the boiler if the Modbus

signal fails. If E8 is in Standby

Mode, BCM will cycle the

pump with the boiler. If E8 is in

Day Mode, the E8 will

continuously run the pump.

The E8

is the primary

controller and the BCM

allows monitoring, and the

BCM

will take over the boiler

if E8 fails. If E8 is in Standby

Mode, E8 will cycle the pump

(must use Enable/Disable). If

E8 is in Day Mode, the E8

will continuously run the

pump.

NOTES:

1)

DO NOT set the 3-Position Switch to Position I.

2) Set the 3-Position Switch to Position

O ONLY when controlling Boilers from an external

Controller via Modbus Communication. See

Paragraph 3.1.2 of the E8 Controller User

Manual (GF-115-C) for setting HEAT Modes.

3) Position

II is the Default position for the 3-Position Switch. Ensure it is set to this position

when it arrives from the Factory. See

Paragraph 3.1.2 of the E8 Controller User Manual

(GF-115-C) for setting HEAT Modes.