1.8.3 Water Quality Requirements

NOTE

For additional information concerning water quality and treatment,

refer to AERCO technical documents Glycol Directive and AERCO

Piping Application Guide (GF-136-P).

Unsuitable heating system water can cause the formation of scale or sludge, which affects system

efficiency. It can also cause corrosion and reduce life of the heat exchanger.

You must follow guidelines for boiler water quality.

Thoroughly flush the system prior to filling.

Follow the cleaning instructions.

Never use water to fill the heating system that has been treated by reverse osmosis,

deionization, or distilled water in order to soften the water.

Do not use inhibitors or other additives unless approved by AERCO for that purpose.

When frost protection of the heating system is desired, only use AERCO-approved

antifreezes. The allowed maximum concentration is 50%.

When using oxygen-permeable pipes, e. g. for under floor heating systems, you must

separate the system from the boiler using plate heat exchangers.

Close the valves of the boiler while flushing the system, do not introduce any system

cleaner into the boiler loop. Flush system thoroughly to remove all system cleaner before

filling boiler.

Approved antifreeze (maximum concentration of 50%):

Rhomar RhoGard Mutli-Metal (AL safe)

Noble Noburst AL

Approved system cleaners:

Noble Noburst Hydronic System Cleaner

Fernox F3 Cleaner

Rhomar Hydro-Solv 9100

The system cleaners from NoBurst, Rhomar, and Fernox are NOT to be used in the boiler itself.

The boiler must be closed off (valves closed) from the rest of the system or not connected while

the cleaners are in the system. The system should then be drained and then thoroughly flushed

with clean water to remove all the system cleaner.

Approved inhibitors:

Rhomar Pro-tek 922

Noble Noburst AL inhibitor

AERCO/Sentinel products. See list in GF-136-P, section 2.3 -

System Flushing, Treatment,

and Cleansing.