lost communication with the
modulating gas valve.

Check that valve is powered
and operating correctly.

Check for signal (0-10VDC) on
terminal J11. The unit will
not fire until valve has
proven closed (<=2.0 VDC
signal on terminal J11)

Check ICECON2 fuses

NO DISPLAY ON
ICECON2 CONTROLER

Board requires 24VAC on terminal J2
for operation. Check fuses on both
the control panel and Circuit board
and replace as necessary.

Verify correct wiring, wiring
connections and grounding of the
electrical components.

BOARD WILL NOT
ENTER HEAT MODE

ICECON2 requires 24VAC on terminal J12
to enter heat mode.

Board requires a 2.0 VDC signal on
terminal J11 before initiating trial
for ignition.

Flame has not proven. ICECON2
requires a 24VAC signal on terminal
J22 before entering heat mode. The
controller will use 4 trials for
ignition before indicating “flame
error”.

UNIT WILL NOT
MODULATE

Check for free rotation of the
modulating valve

Check for correct feedback signal

SUPPLY FAN DOES
NOT INGAGE

Check for power on terminal J5 on the
ICECON2 controller. If power is trace
unit wiring as per diagram to
determine fault.

Check for power on terminal J6. If
power is not present trace wiring as
per diagram to determine fault.

If power is present on J6 but not J5
the system is not calling for the
supply air.