CE – Conformity

The xL System described in this manual conforms to the requirements of the Council Directive
89/336/EEC – The EMC Directive and 73/23/EEC – The Low Voltage Directive. 1999/5/EC-The
R&TTE Directive. To maintain compliancy with this directive, it is essential to adhere to the installation
recommendations described within this manual.

Standards to which Conformity is Declared:

CISPR 11:2003 / EN55011:2003 – Class A – Limits and methods of measurements of radio
disturbance characteristics for industrial, scientific and medical (ISM) radio-frequency equipment.

CISPR 22:2003 / EN55022:2003 Class A – Limits and methods of measurement of radio
disturbance characteristics of information technology equipment.

EN 50130-4:1995 – Electromagnetic compatibility – product family standard: Immunity requirements
for components of fire, intruder and social alarm systems.

EN 60950-1: 2001 – Safety of Information Technology

TBR21:1998 – Terminal Equipment Attachment requirements for the connection to the analogue
PSTN

Standard Description

Severity

Applied

Performance

Criteria

IEC 1000-4-2
EN 61000-4-2

Electrostatic
Discharge

6kV Contact Discharge (direct and indirect)
8kV Air Discharge

A
A

IEC 1000-4-3
EN61000-4-3
ENV
50140/240

Radiated RF
Immunity

10V/m, 80-2000 MHz, 1 kHz 80% AM
modulation
10V/m 80-2000 MHz, Pulse Modulation with
1 Hz Square

A


A

IEC 1000-4-4
EN 61000-4-4

Electrical Fast
Transient

+/-2kV on AC lines
+/-1kV on DC & I/O lines

A
A

IEC 1000-4-5
EN 61000-4-5

Surge
Withstand
Immunity

+/-2kV Common Mode on AC lines
+/- 1kV Differential Mode on AC Line

+/-2kV Common Mode on I/O lines.

A
A
A

IEC 1000-4-6
EN 61000-4-6
ENV 50141

Conducted RF
Immunity

10Vrms, 0.15-100 MHz, 1kHz 80% AM
modulation on AC lines
10Vrms, 0.15-100 MHz, 1kHz 80% AM
modulation on I/O lines
10Vrms, 0.15-100 MHz, Pulse Modulation
with 1 Hz Square.

A

A

A

IEC 1000-4-
11
EN61000-4-
11

Dip

Dropouts



Voltage
Variation

60% for 0.5, 1, 5 & 10 cycles repeated 3
times every 10s
30% for 0.5, 1, 5 & 10 cycles repeated 3
times every 10s
100% for 0.5, 1, 5 & 10 cycles repeated 3
times every 10s.

+10%, -15% for AC from nominal

A

A

A

A

IEC 1000-3-2
EN61000-3-2

Harmonic
Current
Emissions

Class A (Other), Class B (Portable
Equipment), Class C (Lighting Equipment) or
Class D (Special Current Waveform)

PASS

IEC 1000-3-3
EN61000-3-3

Voltage
Fluctuation
and Flicker in
Low-Voltage
Supply
Systems

Voltage Fluctuation
Flicker

PASS
PASS

Not verified by UL