Elevator control, Hardware wiring requirements, Cab reader – Keri Systems Doors.NET Manual User Manual

Page 387: Door controller and 4x4s

Advertising
background image

Doors.NET Reference Manual

- 387 -

Elevator Control

Doors.NET supports Elevator Control when using NXT Mercury Powered controllers
and NXT 4x4 modules or GIOX units. For many different sized elevator applications this
can be an extremely cost-effective solution. With one 4x4 module wired into each bus
and using the four outputs on an NXT 4-door controller you can provide elevator control
access for up to 20 floors per 4-door controller and 10 floors per 2-door controller.

Using GIOX modules you can control up to 128 floors using either 2 or 4 door controllers.
You can use a maximum of two GIOX modules per controller, so if they are both fully pop-
ulated with 8 outputs cards each GIOX can provide control for 64 floors, giving you a
maximum total of 128 floors.

One reader is situated in the elevator cab and this one reader is responsible for all
access requests to all the floors. This Application Note will describe the process for con-
figuring elevator control for up to 20-floors. It is important to follow these steps in the cor-
rect order to ensure proper operation of your elevator control system.

Hardware Wiring Requirements

Cab Reader

The reader situated inside the elevator cab must be wired into bus 1 of the controller for
proper operation.

2-Door Controller and 4x4s

For a 2-door controller handling up to 10 floors:

Floor

Device

Wiring Loca-

tion

Terminal

Block

Default Output

Designator

Default Input

Designator

1

2-D Con-

troller

Port 1

TB1

Output 0.1

Input 0.1

2

2-D Con-

troller

Port 2

TB3

Output 0.2

Input 0.2

3

4x4

Bus 1 - Port

1

TB22

Output 5.1

Input 5.1

4

4x4

Bus 1 - Port

2

TB23

Output 5.2

Input 5.2

5

4x4

Bus 1 - Port

3

TB24

Output 5.3

Input 5.3

Advertising