- 55 -

The system calendar option is licensed separately but include more features than
just the backup option.

Program Improvements:

l

If a user executed the same save command, multiple times, back-to-back, com-
mand communication would fail and report a timeout. Checks have been imple-
mented to filter out multiple instances of the same command.

l

The NXT Gateway failed with an exception if a RIM or a GIOX firmware upgrade
command was performed multiple times, back-to-back. Checks have been imple-
mented to filter out multiple instances of the same command.

l

Corrected an error when creating a Trigger in local linkage, if you select a variable
to be false and select save, the "false" value would not be saved.

l

The Time Stamp when viewing controller status was not updating. The NXT Gate-
way has been updated to include sending the timestamp as part of the controller
status report.

l

Improved NXT Gateway data throughput when handling large numbers of readers
and cardholders.

l

Added checking to the System Update process to verify that if there has been no
changes to a database, there is no need to update that database.

l

The software installer now checks for an open client before performing an install-
ation. If a client is open, the installer presents a dialog box requesting the client be
closed before the installation can continue.

l

Improved the process by which the software installer removes a previous install-
ation prior to performing a new installation.

l

Corrected the Gateway Wizard tab order to correctly follow the flow of operations.

l

The software installer did not properly configure the UK English language set for
operators who selected UK English.

l

Improved cardholder access rights configuration. Following a specific set of oper-
ations, cardholder access rights could be reset to default values.

l

With the Time and Attendance option enabled, the Rollcall/Tracking feature did not
properly follow cardholder state through In/Out readers.

l

When in monitor mode, the Gateway would continue to send events to the Applic-
ation Server when the Application Server was off line. The Gateway now recog-
nizes if the Application Server is off line and halts monitoring mode.

l

The Application Server time stamp showing in the Auto-config status message did
not match the computer's time. It was off by the difference between local time and
GMT. The Server time now correctly adjusts for the GMT difference.

l

If you let the system auto generate PINs, you could not change from default value
of 6 digits. The program should now allow you to set the number of digits and then
auto generate PINs.