LAARS Heating Systems

SECTION 6.
Electrical Connections

6A. Electrical Connections

All electrical wiring must conform to local codes

and/or the 1). National Electric Code or 2). Canadian

Electrical Code - Part 1.

The unit must be electrically grounded in

accordance with the requirements of the authority

having jurisdiction or, in the absence of such

requirement, with the 1). National Electrical Code.

ANSI/NFPA NO.70- latest edition, or the CSA

Standard C22.1 “Canadian Electrical Code - Part 1”.

Single pole switches, including those of safety

controls and protective devices must not be wired in a

grounded line.

All electrical connections are made in the field

wiring box which is located on the right side of the

unit.

Figure 18. Single Zone.

Figure 19. Zoning with Zone Valves.

Figure 20. Zoning with 3 Wire Zone Valves.

Figure 21. Zoning with Circulators

NOTE: All internal electric components have

been pre-wired. No attempt should be made to connect

electric wires to any other location except the wiring

box as described below.
1.

Main power
Connect a 15 amp fused 120 volt supply to the

main power switch illustrated (hot leg is

connected directly to switch). Neutral leg to

white wire. Ground wire can be connected to the

grounding screw in the box or on the switch.

2.

For single zone installations, connect room

thermostat (T-T) wires to the red and white/red

wires. Connect circulator (120 volt, 5 amps

maximum) between the blue wire and the white

wire (neutral) (see Figure 18). Set thermostat

anticipator to 0.9 amps.

3.

Zone Valves and Thermostats: Fig 19 (Fig 20 for

3 wire zone valve such as TACO) or DC

magnatrol valves.
Install external 24 volt transformer of sufficient

V.A. to power combined load of zone valves.

Consult zone valve manufacturer’s instructions.

Connect circulator (120 volt, 5 amp maximum)

between the blue wire and the white wire (neutral).

4.

Multi-Zone/ Multi-Relay-Circulator

Installations: Multiple circulators must not

exceed 5 amps when connected to blue wire.

Blue wire must be used on all HW series (see

Figure 21).
NOTE: On zone valve systems such as Taco,

Automag and others which do not have isolated (dry)

contact end switches, a single pole isolating relay must

be utilized. (see Figure 20).

LEGEND

S1 Disconnect Switch

TH1

24-Volt Thermostats

R1 Zone Relays.

Honeywell R845A or
equivalent.

TH2

R2

TH3

R3

C1 Zone Circulators -

Max 5 AMP
120 VAC.

ZV1 Zone Valves.

Honeywell V8043 or
equivalent.

C2

ZV2

C3

ZV3