Out of production – LAARS HP-M2 Series - Installation, Operation and Maintenance Instructions User Manual

Page 7

Advertising
background image

H Series

Page 7

Height Lateral

Vent Connector Diameter (A & D)

5"

6"

Appliance Rating in MBH

H

L

Fan Assist

Fan Assist

(ft)

(ft)

Min

Max

Min

Max

6

0

85

249

126

373

2

85

156

123

231

4

102

152

6

114

147

8

0

83

273

123

412

2

83

176

121

261

5

107

168

8

122

161

10

0

82

293

120

444

2

82

193

119

287

5

105

185

10

15

0

80

325

116

499

2

80

225

115

337

5

102

216

10

128

201

20

0

78

346

114

537

2

78

248

113

375

5

100

239

10

125

223

30

0

76

372

110

584

2

76

281

109

429

5

98

271

10

122

255

15

Table 1.

Capacity of Tybe B Double-Wall with Single Wall

Metal Connectors Serving a Single Category I Appliance.

NOTE: TABLES APPLY TO MODEL H(W)-M2 130
(CATAGORY 1) APPLIANCES ONLY.

Table 2.

Capacity of Masonary Chimney Flue with

Type-B Double Wall Flue Connector Serving a

Single Category Appliance.

NOTE: DERATE "FAN MAX" CAPACITY IN TABLE 2 BY
20% WHEN SIZING FLEXIBLE METAL FLUELINERS.

Height

Lateral

Type B Double Connector Diameter to be used with

chimney areas within the size limits at bottom

7"

8"

Appliance Rating in MBH

H

L

Fan Assist

Fan Assist

(ft)

(ft)

Min

Max

Min

Max

10

2

68

519

15

2

53

475

64

613

5

99

594

10

126

565

20

2

51

522

61

678

5

80

503

95

658

10

122

627

30

2

47

581

57

762

5

75

561

90

741

10

115

709

50

2

51

840

5

83

819

Minimum Internal

Area of Chimney

Square Inches

50

63

Maximum Internal

Area of Chimney

Square Inches

269

352

Figure 5. Tiled Lined Chimney. Masonry Chimney
Serving a Single Category I Appliance (see Table 2).