Out of production – LAARS HP-M2 Series - Installation, Operation and Maintenance Instructions User Manual

Page 35

Advertising
background image

H Series

Page 35

WITH A CALL FOR HEAT RESET
BOILER CONTROL BY SWITCHING
OFF BOILER SWITCH FOR 15 SECS.
AND THEN ON AGAIN.

AFTER TWO SECONDS DOES
GREEN POWER LIGHT COME ON?

REFER TO GENERAL TROUBLE
SHOOTING SECTION FIGURE 24

PUMP OPERATES?

YES

YES

NO

NO

AFTER FIVE MINUTES ARE
ANY RED LIGHTS FLASHING?

120 VOLTS AT PUMP PLUG?

YES

NO

LIMIT CIRCUIT OPEN
- SEE FIGURE 25

PURGE - SEE FIGURE 26
VALVE - SEE FIGURE 29

24 VOLTS AT CONTROL
(CN6) PLUG PIN #7

NO

YES

REPLACE
2400-224

YES

120 VOLTS AT
PUMP MOTOR

REPLACE
PUMP
CARTRIDGE

YES

NO

CHECK
WIRES TO
PUMP

Р

Р

Р

Р

Р

Р

NO

Р

Р

Р

Р

Р

Р

Р

NO CALL
FOR HEAT

Figure 30. Checking Internal Pump.

OUT OF

PRODUCTION